Design of spectroscopy-based detector for SO2 concentration in SF6 decomposition products
-
Graphical Abstract
-
Abstract
Aiming at the detection of SO2 concentration in SF6 decomposition products in electrical equipment, the design of ultraviolet absorption spectrum analysis module and data processing method were studied. Low power consumption pulsed xenon lamp light source was used to shorten preheating time. A long optical path gas absorption cell with multiple reflections was designed to effectively shorten the response time. The gas consumption was reduced, and the light source and micro spectrometer were directly coupled with the gas chamber, so that the stability was better. The SO2 concentration was inversed in the 280 nm~320 nm spectral band. The partial least squares regression multiple correction method was used to establish a regression model for the differential absorbance of SO2 spectral band and the SO2 concentration, and the errors of the model was less than 0.5 μL/L. The principle prototype was designed, and the feasibility of the design scheme was verified by experiments.
-
-